Page 330 - International safety guide for oil tankers and terminals
P. 330

INTERNATIONAL SAFETY GUIDE FOR OIL TANKERS AND TERMINALS



                                    terminal or plant central control room or central supervisory centre,
                                    battery size usually provides for loss of primary power for a minimum
      ---ใช้เพื่อการศึกษาเท่านั้น---
                                    period of 8 hours and for at least 12 hours if the supply is not reasonably
                                    reliable.

                                    The specification for the detection and alarm systems on terminalsิชย์นาวี
                                    In auxiliary and remote station systems where trouble signals from the
                                    loss of local operating power might not be transmitted to the receiving
                                    station, a 60 hour emergency power supply capacity is usually required in
                                    order that the emergency supply can operate the entire system if the
                                    power is cut over a weekend.




               19.4      Detection and Alarm Systems at Terminals
                         Handling Crude Oil and Petroleum Products


                         19.4.1     General


                                    transferring crude oil and flammable hydrocarbon liquids will depend on a
                                    number of factors that include the following:

                                      The commodities or products transferred.
                                      Tanker size and number berthed per year.
                                                                          ึ
                                      Pumping rates.
                                      The proximity of hazardous equipment with respect to other equipment
                                       or hazards, i.e. equipment spacing, electrical area classification.
                                       The proximity of tankers to the terminal and to hazardous terminal
                                     งสมุด ศูนย์ฝกพาณ
                                       equipment.
                                      The proximity of the terminal to residential, commercial or other
                                       industrial properties.

                                      The installation of emergency isolation valves.
                                      The number and nature of fixed fire extinguishing systems that are
                                       connected to detection and alarm systems.

                                      Whether the terminal is continuously manned or periodically
                                       unmanned.
               งานห้อ                   Proximity to any outside emergency response units, and their capacity,
                                       The ability of the emergency response unit at the terminal or within

                                       the terminal’s organisation to provide a timely and effective response.
                                       availability and time of response.

                                       Requirements imposed by local regulatory bodies.
                                       The desired degree of protection beyond regulatory requirements.
                                       The degree of effective protection that a particular manufacturer’s
                                       detection and alarm system offers.

                                    The alarm system should have the capability to raise local audible and
                                    visual alarms and possibly a general alarm if the terminal is manned and
                                    depending upon local circumstances. It should indicate an alarm at a
                                    continuously attended central fire control panel showing the location of
                                    the activated detection and fire extinguishing system. Where fixed gas
                                    detection equipment is installed or the detection system covers more than
                                    a single detection zone, the panel should indicate the location of the
                                    activated gas detector.