Page 303 - International safety guide for oil tankers and terminals
P. 303

TERMINAL SYSTEMS AND EQUIPMENT



                                               Therefore, even if the resistance of the flange drops below the
                                               1,000 ohms quoted above due, for example, to ice, salt spray or
      ---ใช้เพื่อการศึกษาเท่านั้น---
                                               product residue, any current flow will still be limited to a few
                                               milliamps as the potential difference across the flange will be far
                                               less than is required to initiate an arc during connection or
               งานห้องสมุด ศูนย์ฝกพาณิชย์นาวี
                                               disconnection of loading arms or hoses. Conversely, trying to
                                               earth (ground) a low voltage/high current circuit with a bonding
                                               cable is difficult, even if a very low resistance cable is used. The
                                               total resistances of the cable circuit connections and any
                                               switching device, combined with the availability of a very large
                                               current, will effectively prevent the potential difference between
                                               the ship and shore becoming zero and will render this circuit
                                               ineffective as a means of eliminating ship/shore currents in
                                               loading arms.

                                               Typical DC insulation testers are often arranged with a user
                                               selectable test voltage (500/250/50 V etc) but are not normally
                                               accurately ranged or capable of adequately applying voltages to
                                               resistances as low as 1,000 ohms. These instruments are
                                               therefore not best suited for routine testing, but could be used for
                                               new installations where there will be no contamination of the
                                               flange and insulation readings will be many times higher. Routine
                                               testing should therefore be undertaken with an insulation tester
                                               specifically designed to have a typical driving voltage of 5 V or
                                                                          ึ
                                               more when applied to a resistance of 1,000 ohms or greater.
                                               It is recommended that handheld multimeters are not used for
                                               resistance testing of insulating flanges. Although it is understood
                                               that there may be multimeters with a capability to undertake this
                                               testing, they do not typically apply sufficient test energy to be
                                               effective in determining flange resistance, and may therefore
                                               falsely show a flange as having adequate resistance. However,
                                               should a potentially suitable multimeter be identified, it is
                                               recommended that users take care to verify that the equipment
                                               meets the strict interpretation of the recommendations contained
                                               in this Section before carrying out the tests.


                                 17.5.5.3      Safety
                                               Testing should be undertaken with instruments and methods
                                               selected to be compatible with any hazardous area associated
                                               with the location of the flange. Where testing of an insulating
                                               flange is carried out in a hazardous area with testing equipment
                                               not certified for use in such an area, the testing should be
                                               performed under the control of a Permit to Work (see
                                               Section 19.1.3).




                    17.6      Earthing and Bonding Practice in the Terminal

                              Earthing and bonding minimises the dangers arising from:

                                Faults between electrically live conductors and non-current carrying metalwork.
                                Atmospheric discharges (lightning).
                                Accumulations of electrostatic charge.








                                                   © ICS/OCIMF/IAPH 2006                                       269
   298   299   300   301   302   303   304   305   306   307   308